Krietsch A., Romahn T., Scheid M., Krause U., 2013, Modified Setup of 20-L-Sphere for the Determination of Safety Characteristics of Nano Powders, Chemical Engineering Transactions, 31, 805-810.
This paper describes a modified experimental setup for the test apparatus 20-L-Sphere (also known as 20-L Siwek Chamber), that enables the test samples to be kept under inert atmospheric conditions nearly until ignition. This setup was designed to allow the determination of safety characteristics of nanopowders under most critical circumstances (e.g. minimisation of the influence of oxidation before the test itself). The aim of this modification was to determine, whether or not the current setup and procedures underestimate the explosion violence and ignitability of nanopowders. The work includes experimental results of micrometer dusts to validate the modified setup. Moreover first results of nanometer iron and aluminium dusts are presented, which were kept at inert conditions until shortly before the ignition. The tested nano iron was found to react pyrophoric, as soon as it gets in contact with air, while the tested nano aluminium did not generally show such behaviour.